QC Notes - Cable Shield, Cable Gland, Fastener Torque Value, Sizing of Cable, Grounding System || Aramco Standard

QC-SKILLS
By -
0

 

QC Notes - Cable Shield, Cable Gland, Fastener Torque Value, Sizing of Cable, Grounding System || Aramco Standard

This article is about Cable Shield, Cable Gland, Fastener Torque Value, Sizing of Cable, Grounding System and focusing to the engineers, technicians and supervisors. You will find lot of documents related to this article. Just navigate our website www.QCSKILLS.com and find more articles. Please! Do not forget to subscribe our You tube channel also. Thanks in Advance.

Cable Shield, Cable Gland, Fastener Torque Value, Sizing of Cable, Grounding System

Cable Shield as per ARAMCO & International Standard:

Prevent Electromagnetic Electrostatic  Interference from being endued into the inner wire conductor.

- Design and installation of power and wiring system for instrumentation shall be in accordance with NFPA 70 and NEC.

- Fireproofing of cable in fire hazardous area shall be in accordance with SAES-B-006 (Aramco Standard).

- Shielded cables shall be used as required to reduce electrostatic noise. The shield shall be grounded at one point only.

- Field Bus Cable shall Comply with IEC 61158-2 (Type A)

- Cable Insulation thickness 0.38 mm PLTC/ITC

- TC Cable thickness 0.64 mm

- Light blue color coding shall be used to identify intrinsically safe wiring the preferred practice is to specify intrinsically safe interconnecting cable with blue outer jacket. Alternative blue sleeweves slipped over the jacket.

- At all the points of termination may used to identify I.S. wiring.

- If used for connections of equipment to ground rods or ground grid to be minimum 25 mm2 (# 4 AWG).

- Intrinsically safe system shall be used in zone 0 hazardous area.

- Thermal send have to use in trench before started send bedding.

Guide Lines to identify T/C and T/C Extension wires:

For Extension wires having insulation color as per ANSI MC96.1 (American National Standard Institute). The negative wire is always RED colored as per ANSI.

Cable Gland as per ARAMCO & International Standard:

-For Hazardous & Non Hazardous locations shall be in accordance with BS 6121 or BS 50262.

-Cable Gland: Cable glands are used to protect Mechanical damage. To give earth continuity and for

entering it a junction box & MCC etc. For PILC (Paper Insulation Copper Conductor) cables lead covered are used because in refinery, hydrocarbon gases will damage the PVC insulation, for this purpose lead cover is used, for these purpose plumbing type glands are used.

- In Explosion proof areas double compression glands are used to avoid these gasses entering in the electric at apparatus.

Fastener Torque Value:

M8                    14 ~ 16 NM

M10                  26~ 33 NM

M12                  45~ 58 NM

 

Sizing of Cable as per ARAMCO & International Standard:

0.75 mm2          18AWG

1.0 mm2            17AWG

1.5 mm2            16AWG

2.5 mm2            14AWG

4.0 mm2            12AWG

6.0 mm2            10AWG

10 mm2             08AWG

16 mm2             05 AWG

25 mm2            04AWG

35 mm2             02 AWG

50 mm2            1/0AWG

70 mm2            2/0AWG

120 mm2           4/0AWG

 

Grounding System as per ARAMCO & International Standard:

- Ground rods 2.4 meter minimum length.

- Cathode protection material is used galvanized steel.

- Individual Ground rod maximum resistance should be 2.5 Ohm.

- For copper or copper jacketed steel rods is a minimum of 16 mm2 in diameter or 19 mm2 in diameters.

- Earth Tester is used for measuring of earthling system.

- Underground wire for grounding to wire connections shall be cadweld or thermoweld. Compression connector shall not be used.

- Shields wires shall be grounded only at the one point for the signal cables.

- Shields and armor of power cables shall be grounded at both ends.

- If used for connections of equipment to ground rods or ground grid be minimum 25 mm2 (# 4 AWG).

- Metallic cable trays shall be bonded at both end points and a minimum of every 25 Meter to the local ground grid.

- If buried / used for grids or interconnections of ground rods to be minimum 70 mm2 (2/0AWG).

- Be copper or copper jacketed steel or galvanized steel or copper jacketed steel shall meet the requirements of UL 476 (Underwriters Laboratories).

- Power Applications:   Metal cable trays must be grounded and eclectically continuous systems as per NEC article 318.

- Non-Power Applications: Cable tray systems containing conductors outside the scope of NEC Article 250 (such as communications, data, signal cables, etc.)

Post a Comment

0Comments

Post a Comment (0)